- 32 analog inputs (16-bit, 250 kS/s)
- 4 analog outputs (16-bit, 833 kS/s), 48 digital I/O (32 at up to 1MHz), and 32-bit counters
- NI Signal Streaming for sustained high-speed data streams over USB; OEM version available
- Compatible with LabVIEW, LabWindows/CVI, and Measurement Studio for Visual Studio .NET
- NI-DAQmx driver software and NI LabVIEW SignalExpress LE interactive data-logging software
Data Sheet
The National Instruments USB-6229 is a USB high-performance M Series multifunction data acquisition (DAQ) module optimized for superior accuracy at fast sampling rates.
The USB-6229 is designed specifically for mobile or space-constrained applications. Plug-and-play installation minimizes configuration and setup time, while direct screw-terminal connectivity helps keep costs down and simplifies signal connections.
This USB-6229 also features the new NI Signal Streaming technology, which provides DMA-like bidirectional high-speed streaming of data across the USB bus. For more information about NI signal streaming, check the Resources tab.
NI also offers a USB-6229 OEM version. Check the Resources tab or use the left navigation to get pricing and technical information.
Driver Software NI-DAQmx driver and measurement services software provides easy-to-use configuration and programming interfaces with features such as DAQ Assistant to help reduce development time. Browse the information in the Resources tab to learn more about driver software or download a driver. M Series devices are not compatible with the traditional NI-DAQ (Legacy) driver.
Application Software Every M Series data acquisition device includes a copy of NI LabVIEW SignalExpress so you can quickly acquire, analyze, and present data without programming. In addition to LabVIEW SignalExpress, M Series data acquisition devices are compatible with the following versions (or later) of NI application software – LabVIEW 7.1, LabWindows™/CVI 7.x, or Measurement Studio 7.x. M Series data acquisition devices are also compatible with Visual Studio .NET, C/C++, and Visual Basic 6.
Additional Product Information
Specifications Documents
Specifications Summary
| General | |
| Form Factor | USB |
| OS Support | Windows |
| Measurement Type | Quadrature encoder, Voltage |
| DAQ Product Family | M Series |
| Analog Input | |
| Number of Channels | 32 SE/16 DI |
| Sample Rate | 250 kS/s |
| Resolution | 16 bits |
| Simultaneous Sampling | No |
| Maximum Voltage Range | -10..10 V |
| Range Accuracy | 3100 µV |
| Range Sensitivity | 97.6 µV |
| Minimum Voltage Range | -200..200 mV |
| Range Accuracy | 112 µV |
| Range Sensitivity | 5.2 µV |
| Number of Ranges | 4 |
| On-Board Memory | 4095 samples |
| Analog Output | |
| Number of Channels | 4 |
| Update Rate | 833 kS/s |
| Resolution | 16 bits |
| Maximum Voltage Range | -10..10 V |
| Range Accuracy | 3230 µV |
| Minimum Voltage Range | -10..10 V |
| Range Accuracy | 3230 µV |
| Current Drive (Channel/Total) | 5 mA |
| Digital I/O | |
| Number of Channels | 48 DIO |
| Timing | Hardware, Software |
| Maximum Clock Rate | 1 MHz |
| Logic Levels | TTL |
| Maximum Input Range | 0..5 V |
| Maximum Output Range | 0..5 V |
| Input Current Flow | Sinking, Sourcing |
| Programmable Input Filters | Yes |
| Output Current Flow | Sinking, Sourcing |
| Current Drive (Channel/Total) | 24 mA/896 mA |
| Watchdog Timer | No |
| Supports Programmable Power-Up States? | Yes |
| Supports Handshaking I/O? | No |
| Supports Pattern I/O? | Yes |
| Counter/Timers | |
| Number of Counter/Timers | 2 |
| Resolution | 32 bits |
| Maximum Source Frequency | 80 MHz |
| Minimum Input Pulse Width | 12.5 ns |
| Logic Levels | TTL |
| Maximum Range | 0..5 V |
| Timebase Stability | 50 ppm |
| GPS Synchronization | No |
| Pulse Generation | Yes |
| Buffered Operations | Yes |
| Debouncing/Glitch Removal | Yes |
| Timing/Triggering/Synchronization | |
| Triggering | Digital |
| Physical Specifications | |
| Length | 26.67 cm |
| Width | 17.09 cm |
| Height | 4.45 cm |
| I/O Connector | Screw terminals |
Extended Warranties
National Instruments designs and manufactures all products to minimize failures, but we know unexpected failures can still occur. Extended warranties provide a fixed economical price at the time of system purchase covering any repair costs for up to three years.
- Significant cost savings compared to individual repair incidents
- Fault location, diagnostics, and repair by NI any time the system product fails
- All parts and labor costs covered as well as any adjustments needed to bring the hardware back to manufacturing specifications
Calibration
NI recognizes the need to maintain properly calibrated devices for high-accuracy measurements. We provide manual calibration procedures, services to recalibrate your products, and automated calibration software to calibrate many of our measurement products.
Training
NI training is the fastest, most certain route to productivity with NI tools and successful application development.
Repair Services
- You can return your registered product under warranty at no additional labor and parts cost. NI offers fault location, diagnostics, and repair any time the system fails as well as any adjustments needed to bring the hardware back to manufacturing specifications.
- Contact us to obtain a Return Material Authorization (RMA) form and shipping instructions
- View your RMA support request status online
- Register your product
Technical Support
www.ni.com/support
|