Customer SolutionsSCXI and LabVIEW Test Traulsen Refrigerators and Freezers
Author(s):Eubank Jacobs, Traulsen
Industry:Electronics
Product:Data Acquisition, LabVIEW, Signal Conditioning
The Challenge:Ensuring that every refrigerator and freezer shipped meets standards set forth by the National Sanitation Foundation (NSF).
The Solution:Using LabVIEW in a PC-based instrumentation system to monitor and control four rooms containing eight test stands where refrigeration design engineers test Traulsen refrigerators and freezers.Traulsen sells more reach-in refrigerators and freezers to the restaurant market than any other company in the world. Their customers include McDonald’s, Outback Steakhouse, Denny’s, Marriott, and K-Mart. To make the "preferred vendor" lists for these customers, Traulsen must ensure that every refrigerator and freezer they ship meets standards set forth by the National Sanitation Foundation (NSF). These guidelines require that cabinet air temperature not exceed 40°F for refrigerators with a maximum compressor operating time of 70 percent. Freezers have a maximum allowed temperature of 0°F with a maximum compressor operating time of 80 percent. To test units for guideline adherence, Traulsen needed a PC-based instrumentation system to monitor and control four rooms containing eight test stands at their site in Grand Prairie, TX. These test stands are where refrigeration design engineers test Traulsen refrigerators and freezers. The most difficult part of building a PC-based test system to ensure compliance with NSF standards was finding a combination of hardware and software to acquire, analyze, and present the data. Our first data acquisition system, installed in August 1992, had a parallel port interface and DOS-based, menu-driven software," said Tom Yingst, Vice President of Engineering. "The system had a plug-in board and software that interfaced to a box on the wall. The whole system was ancient and unworkable, and we started looking for something better." "Lynda originally developed a LabVIEW system to run on our older data acquisition system," said Yingst. "So we set up two test rooms to run the LabVIEW systems. When it came time to expand the system to include the two remaining rooms, we reached a fork in the road. We could finish the system using the old hardware, or we could convert the entire system to National Instruments. We decided to go with National Instruments because their hardware was more accurate. Plus, the modular, open architecture gives us the flexibility to adapt the system to our changing needs." Each test stand has 21 signals. Pressure transducers monitor the refrigerant suction and discharge pressure. Two transducers monitor the total current and the compressor current of the unit under test. Another transducer monitors the voltage of the unit under test. SCXI also multiplexes signals from 16 thermocouples that monitor temperatures of the condenser, evaporator lines, discharge, refrigerator section, and freezer section. LabVIEW controls the temperature and humidity in each test room using the SCXI-1160 relay module. When all eight stations are running simultaneously, SCXI controls 12 relays, multiplexes 160 pressure, temperature, and voltage signals, and sends them to LabVIEW for analysis. Traulsen laboratory technicians who use the system every day are finding additional benefits to converting to SCXI. "SCXI is versatile and easily expand-able, and the shielded aluminum is just great," says Dan Howard, laboratory technician at Traulsen. "With the old hardware, we’d have to replace the back of the board because the pins kept breaking- plus, they didn’t have any fans to cool the board." "Once we get the data flowing on this system, it is just fabulous," said Yingst. "We’ve started buying Gateway computers, because you get one general purpose application software package for free and can buy more at a reduced rate. So, every machine in the place comes with Microsoft Excel loaded on it. One of the strong points of LabVIEW is that it can acquire data and analyze it, or can output the data using DDE or file I/O so other, general purpose software programs can be used for analysis. Test reports now consist of data acquired with LabVIEW, copied onto a disk, and routed to the project engineer. He can manipulate it with Excel to his heart’s content." Project engineers can view the test data in Excel as the tests are running. Engineers can also start and stop test stations without interrupting other tests in progress. And what of the older DAQ system? "It’s sitting on a shelf," said Yingst, "and will be used for very simple production test line auditing." View the entire user solution in Adobe Acrobat PDF format. |